 CMA Filter: Robust, IEC-Compliant,
 Ultra-Low Latency Feature Tracking
 for IoT Applications
 Author: Dr. Sanjeev Sarpal

 Application note (ASN-AN032)                                                                                        October 2025 (Rev 3)


Synopsis
Reliable real-time tracking of sinusoidal waveforms is essential across many application domains, from power quality
monitoring to IoT communications. International standards such as IEC 61000-4-30 (dip–swell detection), IEC 61000-
4-7 (harmonic measurement), IEEE 1547 (distributed energy resources), and IEC 61851 (EV charging) demand ultra-low
latency detection and feature extraction, often within a half-cycle.

Meeting these requirements with conventional FIR and IIR filters is challenging, as achieving a narrow transition band
with an FIR demands very high orders, which increases both latency and computational cost. By contrast, an IIR filter
can offer lower latency, but its non-linear group delay means that latency changes with frequency, and sharper transition
bands come at the cost of overshoot and more sluggish time-domain performance.

This article introduces the Complex Moving Average (CMA) filter — a simple but powerful analytic bandpass that
provides instantaneous amplitude, phase, and frequency with minimal latency. Validated against IEC-compliant dip–
swell test datasets, the CMA demonstrates robust tracking of voltage envelopes and frequency variations with only 9.5
samples of latency, outperforming conventional IIR approaches in real-time compliance scenarios.

Lightweight to implement (three multiplications and two additions per sample), and supported by the ASN Filter
Designer with direct C SDK export, the CMA is deployable on resource-constrained Arm Cortex-M devices as well as
safety-critical Arm Cortex-R platforms with lockstep execution, ensuring deterministic real-time performance with fault
tolerance. These qualities make the CMA a practical building block for applications in smart grids, EV chargers, IoT
predictive maintenance, gas sensing, and wireless communications such as LoRa, ZigBee, Bluetooth, Wi-Fi, and 5G.




       Figure 1 – Real-time envelope tracking on IEC 61000-4-7/-4-30 compliant powerline dataset with a dip event
                    CMA filter output time aligned (10ms group delay) for easier visual comparison.

 © 2025 Advanced Solutions Nederland B.V. All material presented in this document is protected by copyright under international copyright laws.   Page 1
 All specifications are subject to change without notice. The information presented in this document is given in good faith and although every
 effort has been made to ensure that it is accurate, Advanced Solutions Nederland accepts no liability for any typographical errors.
1. Introduction
In the real world, powerline (mains) waveforms are rarely ideal. Although nominally a 50Hz or 60Hz sine wave, they are
continuously shaped by harmonics, switching events, and transient anomalies. Large disturbances can be triggered by
everyday events — for example, a motor or industrial machine starting up and drawing a surge of current, which can
momentarily pull down the grid voltage. Equipment faults, load imbalances, or sudden disconnections can equally cause
the voltage to rise above nominal levels. The result is a voltage dip (a sudden reduction in RMS voltage) or a voltage
swell (a sudden increase), both of which can trip sensitive equipment, disrupt processes, and, in the worst cases,
destabilise the grid.

But dips and swells are not just a power system's problem. The same challenge arises anywhere a sinusoidal waveform
must be monitored in real time. In wireless communications, the requirement is to track carrier envelopes and signal
integrity across technologies such as LoRa, Zigbee, Bluetooth, Wi-Fi, and 5G, where reliable amplitude and frequency
tracking is essential for maintaining link quality. In IoT measurement tasks such as predictive maintenance, vibration
or even acoustic signals, must be tracked in real time to detect early signs of failure. Whether in smart grids, EV
chargers, IoT sensors, or base-station antennas, the requirement is the same: extract and track amplitude, phase, and
frequency reliably and with ultra-low latency.

International standards reflect this urgency. IEC 61000-4-30 requires Class A instruments to detect dips and swells in
power systems within half a cycle (10ms at 50Hz). IEEE 1547 for distributed energy resources and IEC 61851 for EV
chargers demand response within tens of milliseconds. In practice, measurement systems must therefore operate with
ultra-low latency, extracting useful features from just a handful of samples.

Conventional filter approaches — Butterworth, Chebyshev, Gaussian FIR, and similar designs — can be used, but when
the sampling rate is high and the passband is low, they quickly fall short. Both FIR and IIR band-pass filters still output
a sinusoid, requiring rectification and smoothing that adds latency. FIRs demand high orders for sufficient narrowband
selectivity, while IIRs, though more compact, suffer from non-linear group delay means that latency changes with
frequency, and sharper transition bands come at the cost of overshoot and more sluggish time-domain performance.
These drawbacks make them poorly suited to sub-cycle detection.

What is needed is a method that can deliver the essential properties of the fundamental waveform — amplitude, phase,
and frequency — with minimal delay, while naturally rejecting DC offsets and harmonics. This article introduces the
Complex Moving Average (CMA) filter as a suitable method: mathematically elegant, computationally efficient, and
practical for deployment on embedded processors ranging from low-power Cortex-M devices to Cortex-R lockstep
platforms for mission-critical grid and industrial applications.

The importance of robust and ultra-low latency feature tracking continues to grow as grids, vehicles, and industrial
systems become more interconnected and standards-driven. Voltage dips and swells remain one of the most common
causes of equipment malfunctions, from tripped EV chargers to disrupted industrial processes and unexpected
downtime in automated plants. In smart grids and distributed energy systems, poor tracking can mask real disturbances
or trigger false alarms, undermining both reliability and compliance.
     International regulations reflect these concerns: IEC 61000-4-30 specifies strict performance for Class A
instruments, IEC 61000-4-7 defines harmonic measurement protocols, and IEEE 1547 and IEC 61851 impose fast
response requirements for grid interconnection and EV charging. These standards not only define how disturbances
must be detected, but also set the benchmark for the design of measurement and control equipment worldwide. Against
this backdrop, there is a pressing need for methods that combine mathematical simplicity with practical deployability,
ensuring that real-time amplitude, phase, and frequency tracking can be achieved across diverse embedded platforms.
The challenge is therefore not just theoretical accuracy, but delivering solutions that can be realised in practice on cost-
sensitive devices. Addressing this challenge is the central focus of the solution presented herein.




 © 2025 Advanced Solutions Nederland B.V. All material presented in this document is protected by copyright under international copyright laws.   Page 2
 All specifications are subject to change without notice. The information presented in this document is given in good faith and although every
 effort has been made to ensure that it is accurate, Advanced Solutions Nederland accepts no liability for any typographical errors.
2. The Moving Average Filter as a Prototype
The moving average (MA) filter is the simplest FIR low-pass prototype. For order 𝑁 (where, 𝐿 = 𝑁 + 1), the impulse
response is given by,

                                                        1
                                                  ℎ[𝑛] = , 𝑛 = 0,1,2,3, . . . 𝐿 − 1                                  (1)
                                                        𝐿

with the transfer function:
                     1
        𝐻(𝑧) =         (1 + 𝑧 −1 + 𝑧 −2 + ⋯ + 𝑧 −(𝐿−1) )                            (2)
                     𝐿
Applying some lateral thinking to the computational challenge, we
see that a much more computationally efficient moving average filter
can be used in order to achieve the same result, namely:

                                1 1 − 𝑧 −𝐿
                         𝐻(𝑧) =                                 (3)
                                𝐿 1 − 𝑧 −1

Upon initial inspection of the transfer function, it appears that the
efficient Moving average filter is an IIR filter. However, analysing the
pole-zero plot of the filter (shown on the right for L=8), we see that
the pole at DC has been cancelled by a zero, and that the resulting
filter is actually an FIR filter, with the same result as Eqn. (4).


Analysing the transfer function, it can be seen that this prototype has regularly spaced notches in its frequency response
at multiples of:

                                                             𝑚𝑓𝑠
                                                      𝑓=         ,          𝑚 = 1,2,3..                              (5)
                                                              𝐿

making it a good candidate for supressing the harmonics of a fundamental.




2.1. Lowpass to Complex Bandpass Transformation
By applying the complex frequency shift transform, we can transform our low-pass prototype into a complex bandpass
filter centred on 𝑓0,

                                                                            2 𝑗𝜔 𝑛
                                                          ℎ𝑏𝑝𝑓 [𝑛] =          ·𝑒 0                                   (6)
                                                                            𝐿

Where, 𝜔0 = 2πf0 /fs . Notice the explicit 2 gain factor in Eqn. (6). This normalisation is required because the complex
shift produces a single-sided (analytic) response that suppresses the negative-frequency content; without it, the
analytic output would be half the correct amplitude.

This can be readily seen via the two-term Fourier series of a real cosine of amplitude 𝐴, i.e.

                                                                      𝐴 jω n 𝐴 −𝑗𝜔 𝑛
                                               A cos(ω0 n) =            e 0 + 𝑒   0                                  (7)
                                                                      2      2

In the ideal, infinite-length case, the spectrum consists of two impulses, each of amplitude 𝐴⁄2 located at ±𝜔𝑜

 © 2025 Advanced Solutions Nederland B.V. All material presented in this document is protected by copyright under international copyright laws.   Page 3
 All specifications are subject to change without notice. The information presented in this document is given in good faith and although every
 effort has been made to ensure that it is accurate, Advanced Solutions Nederland accepts no liability for any typographical errors.
However, when viewed on a spectrum analyser with finite-length windows (see below), these impulses appear as narrow
peaks with some spectral leakage. Nevertheless, the interpretation is the same: the total energy is split equally between
positive and negative frequencies.

When forming the analytic signal, the negative-frequency term is suppressed, leaving only the positive-frequency
exponential of amplitude 𝐴⁄2. To restore the true amplitude, we need to multiply by 2:

                                                             𝑥𝑎 [𝑛] = 𝐴𝑒 𝑗𝜔0𝑛                                        (8)

The magnitude of this analytic signal is exactly 𝐴, i.e. the correct envelope of the original cosine wave.

NB. This is the essence of the analytic signal construction — halve the spectrum by discarding the negative frequencies,
then double the positive frequencies so that amplitude and phase are preserved.




                                                                                                                             0dB (1.0)
                                                                             -6dB (0.5)




Figure 2 - Spectrum of a sinusoid before and after analytic filtering: The blue trace (input) shows a real sinusoid (𝑓𝑜 =
50𝐻𝑧, 𝐴 = 1. Its spectrum has equal positive- and negative-frequency lobes (at ±𝑓𝑜 ), each of amplitude 0.5 or -6dB. The
red trace (output) shows the analytic signal: the negative-frequency lobe is suppressed, and the positive-frequency lobe
is doubled. With the scaling factor of 2 applied, the spectrum now has a single lobe at amplitude 1, corresponding exactly
to the true sinusoidal envelope.


2.2. Complex Moving Average (CMA) filter Definition

Combining the aforementioned concepts and simplifying, we can formally define the CMA as:


                                                                             2 1 − 𝑒 𝑗𝜔0𝐿 𝑧 −𝐿
                                                           𝐻𝑏𝑝𝑓 (𝑧) =         ·                                             (9)
                                                                             𝐿 1 − 𝑒 𝑗𝜔0 𝑧 −1


Taking the inverse z-transform, we obtain the difference equation,

                                                                      2
                                𝑦[𝑛] = 𝑒 𝑗𝜔0 𝑦[𝑛 − 1] +                 (𝑥[𝑛] − 𝑒 𝑗𝜔0𝐿 𝑥[𝑛 − 𝐿])                            (10)
                                                                      𝐿

                                                                                                    2                2 𝑗𝜔0 𝐿
This may be further simplified for implementation, as 𝑐0 = 𝑒𝑗𝜔0 , 𝑐1 =                                , 𝑐2 = − 𝐿 𝑒
                                                                                                    𝐿


                                    𝑦[𝑛] = 𝑐0 𝑦[𝑛 − 1] + 𝑐1 𝑥[𝑛] + 𝑐2 𝑥[𝑛 − 𝐿]                                              (11)

 © 2025 Advanced Solutions Nederland B.V. All material presented in this document is protected by copyright under international copyright laws.   Page 4
 All specifications are subject to change without notice. The information presented in this document is given in good faith and although every
 effort has been made to ensure that it is accurate, Advanced Solutions Nederland accepts no liability for any typographical errors.
What is striking about this result is its implementation simplicity. After all of the theory, 𝐻𝑏𝑝𝑓 (𝑧) reduces to just 3
complex multiplications and 2 complex adds per sample, regardless of 𝐿 — making it an exceptionally lightweight
solution for real-time embedded deployment. The only downside is that the implementation requires Complex arithmetic
support. While many modern C libraries (e.g. CMSIS-DSP) provide basic functionality, the ASN Filter Designer C SDK
library offers full native support for complex filters, so developers can deploy 𝐻𝑏𝑝𝑓 (𝑧) to their application very easily.

                                                                 𝐿−1
As an FIR of length 𝐿, the group delay is: 𝐺𝐷 =                        . For 𝑓𝑠 = 1𝑘𝐻𝑧, 𝐿 = 20 this corresponds to 𝐺𝐷 = 9.5 samples
                                                                   2
or 9.5ms — within the half-cycle (10ms) detection window for 50Hz mains tracking as stipulated by IEC 61000-4-30.

The PSD (Transfer function Estimation) of 𝐻𝑏𝑝𝑓 (𝑧) is shown below. Analysing the plot, it can be seen that while the
filter achieves strong attenuation at DC and at ±𝑓𝑜 , its overall stopband rejection is relatively poor — consistent with
the well-known limitations of a moving average as a low-pass prototype. Nevertheless, as discussed in previous articles,
the moving average has excellent time-domain noise-cancellation properties. Therefore, in reality, as long as inter-
harmonic noise is minimal (as is often the case in power and communications systems), the developed CMA should be
more than sufficient for the applications considered herein.

                                                                           Frequency shift




                                        Figure 3 – PSD (Transfer function Estimation) of 𝐻𝑏𝑝𝑓 (𝑧).


2.2.1.       CMA Characteristics and extras

1. The CMA filter introduces zeros (notches) at DC and at harmonic frequencies 2𝑓0 , 3𝑓0 , 4𝑓0, ⋯, giving strong
   suppression of unwanted components.
2. The passband peak is precisely centred at 𝑓0, ensuring accurate tracking of the fundamental frequency.
3. 3 instantaneous cleaned features: amplitude, phase and frequency.
4. Linear phase and constant group delay – ideal for mission-critical applications that have strict latency
   requirements.
5. 3 complex multiplications and 2 complex adds per sample, regardless of 𝐿.
6. Despite using complex arithmetic, the workload is extremely lightweight, making this a very elegant and efficient
   solution for microcontrollers with floating-point support (e.g. STM32 Cortex-M4/M7/M33).
7. If better stopband attenuation is required, a Kolmogorov-Zurbenko cascade may be employed, which in essence
   cascades R identical MA filters of length L into a single polynomial. Although this will increase the overall latency,
   it’s a very simple way of improving the MA’s frequency domain performance, while retaining its excellent time-
   domain performance.


 © 2025 Advanced Solutions Nederland B.V. All material presented in this document is protected by copyright under international copyright laws.   Page 5
 All specifications are subject to change without notice. The information presented in this document is given in good faith and although every
 effort has been made to ensure that it is accurate, Advanced Solutions Nederland accepts no liability for any typographical errors.
3. Designing the CMA filter in the ASN Filter Designer
The CMA filter can be very easily designed and customised in the ASN Filter Designer using the ASN FilterScript
language. The filter can then be validated via the tool’s signal analyser UI.


1. Set the Sample rate to 1000Hz.




2. Open the ASN FilterScript IDE




3. Paste the following script into the editor, and then Run it.

                 ClearH1;         // clear primary filter from cascade

                 Main()

                 fo=50;
                 L=round(fs/fo);
                 N=L-1; // MA order (length L)
                 Hd=movaver(N,"numeric");
                 Hd=cplxfreqshift(Hd,fo,"symbolic");                 // shift lowpass filter zeros
                                                                     // and make a bandpass
                 Num=getnum(Hd);                     // get numerator coefficients
                 Den=1;                              // get denominator
                 Gain=2*getgain(Hd);                 // get gain




4. Open the signal analyser for testing.




5. Drag and drop your test CSV datafile onto the canvas for analysis and click ‘play’ to start streaming the data.




 © 2025 Advanced Solutions Nederland B.V. All material presented in this document is protected by copyright under international copyright laws.   Page 6
 All specifications are subject to change without notice. The information presented in this document is given in good faith and although every
 effort has been made to ensure that it is accurate, Advanced Solutions Nederland accepts no liability for any typographical errors.
6. Tracking options
    a. Amplitude: set Output Math Function to Abs, alternatively, choose RMS
       if you want RMS amplitude.

      b. Frequency: set output math function to Angle.




7. Setup time domain analytics
       a. Amplitude:




          b. Frequency:




 © 2025 Advanced Solutions Nederland B.V. All material presented in this document is protected by copyright under international copyright laws.   Page 7
 All specifications are subject to change without notice. The information presented in this document is given in good faith and although every
 effort has been made to ensure that it is accurate, Advanced Solutions Nederland accepts no liability for any typographical errors.
4. Results on a realistic dataset
An IEC 61000-4-7/-4-30 compliant powerline dataset was generated, consisting of a 50 Hz waveform sampled at 1 kHz
with programmed dips, swells, and smooth edges, together with injected 3rd, 5th, 7th, and 9th harmonics at specified
amplitudes. To better reflect real-world conditions, the dataset also included natural frequency sway, additive
measurement noise, and a 2% flicker modulation.

This dataset was then processed with the proposed CMA filter. As shown below, the amplitude tracking follows the
envelope very closely across both dips and swells, with only a small latency of 9.5 samples, demonstrating the
suitability of the method for this type of application.




                                                       Figure 4: powerline envelope tracking

Likewise, frequency tracking is also very accurate, where a local, smoothed frequency estimate is obtained by
calculating the gradient of short phase segments (within ± 𝜋⁄2) and then scaling by 𝑓𝑠 ⁄(2𝜋).




      Figure 5: phase waveform of the 50Hz fundamental: Frequency calculated from scaled derivative phase data.


 © 2025 Advanced Solutions Nederland B.V. All material presented in this document is protected by copyright under international copyright laws.   Page 8
 All specifications are subject to change without notice. The information presented in this document is given in good faith and although every
 effort has been made to ensure that it is accurate, Advanced Solutions Nederland accepts no liability for any typographical errors.
4.1. CMA vs. CIIR Butterworth filter

Generating a 10ms (half-cycle dip) at time step 300, we tested the performance of the CMA vs a complex 12th-order
Butterworth IIR filter (CIIR).




                                                        Figure 6: Butterworth CIIR vs. CMA




Analysing the plot, it can be seen that the IIR’s high stopband attenuation delivers the strongest smoothing performance
of the two filters. However, this advantage comes at a cost, as the CIIR exhibits higher latency and a more sluggish
response than the CMA. It is also evident that the IIR fails to track the momentary dip around sample 300. These results
demonstrate that a complex IIR is generally unsuitable for IEC-compliant dip–swell feature tracking.




4.2. Practical considerations

While the simulated dataset shown in Figure 4 illustrates the principle clearly, real-world IoT systems introduce a few
practical considerations. The most important point is the sampling rate tolerance. Low-cost RC oscillators can drift by
±0.5–1%, which will shift the CMA’s nulls away from their ideal positions and noticeably reduce harmonic suppression.
This is why most manufacturers opt for a crystal oscillator with ±50 ppm tolerance (±0.005%), which offers a much
more stable clock at low cost. However, in practice, the oscillator is divided down through prescalers or PLLs to
generate the ADC sampling clock, so the effective sampling frequency may still be off by around ±0.01–0.1%.

A related issue arises when the design length 𝐿 = 𝑓𝑠 ⁄𝑓𝑜 is not an integer. In these cases, fractional values of 𝐿 mean
the filter no longer aligns perfectly with the fundamental, again slightly degrading tracking accuracy. These effects are
usually minor but worth considering in system design. Typical mitigations include oversampling, designing around the
expected clock tolerance, or applying resampling techniques when very high accuracy is needed.


 © 2025 Advanced Solutions Nederland B.V. All material presented in this document is protected by copyright under international copyright laws.   Page 9
 All specifications are subject to change without notice. The information presented in this document is given in good faith and although every
 effort has been made to ensure that it is accurate, Advanced Solutions Nederland accepts no liability for any typographical errors.
Conclusion
This investigation has shown that the complex moving average (CMA) filter is a highly practical solution for ultra-low
latency feature tracking in sinusoidal waveform applications. In wireless communications, the requirement is to track
carrier envelopes and signal integrity across technologies such as LoRa, Zigbee, Bluetooth, Wi-Fi, and 5G, where reliable
amplitude and frequency tracking is essential for maintaining link quality. In smart grids and EV chargers, it enables
fast detection of dips, swells, and flicker for compliance and stability. The same idea extends to IoT measurement tasks
such as predictive maintenance, where vibration or acoustic signals must be tracked in real time. It is equally applicable
to gas sensing with infrared absorption waveforms, or to IEC sine-wave tests in biomedical instrumentation for verifying
amplitude and frequency response. These examples highlight just a few of the areas where clean, real-time amplitude,
phase, and frequency tracking is a core requirement.

The CMA achieves this by transforming a simple MA prototype into a complex analytic bandpass, yielding instantaneous
amplitude, phase, and frequency with minimal delay — well within the IEC 61000-4-30 half-cycle detection requirement.
Tests on IEC-compliant dip–swell datasets confirmed that the CMA can reliably follow voltage envelopes and frequency
variations while maintaining robustness against measurement noise, flicker, and harmonic distortion.

Comparative analysis showed that although complex IIR (CIIR) filters (e.g. Butterworth, Chebyshev) offer higher
stopband attenuation, their added latency and sluggish response make them unsuitable for sub-cycle dip–swell
tracking. In contrast, the CMA achieves the right balance: computational simplicity, consistent linear-phase behaviour,
and suitability for deployment on resource-constrained embedded processors. The implementation is extremely
lightweight, requiring only three complex multiplications and two complex additions per sample, making it
straightforward to realise in C on modern microcontrollers.

Crucially, the entire design, validation, and code generation flow can be carried out in
the ASN Filter Designer, with direct export to the ASN C SDK. Since the SDK provides full
floating-point and complex floating-point support in both single and double precision,
developers can deploy the filter seamlessly on Arm Cortex-M devices for IoT and edge
applications, or on Arm Cortex-R processors with lockstep execution where
deterministic performance and fault tolerance are essential.

Overall, the results emphasise that the CMA is not just a theoretically elegant filter but
a robust and developer-ready building block for IEC-compliant, real-time dip–swell
detection in smart grids, EV charging, and distributed energy resources. In particular, it     Request Download
directly addresses the stringent requirements of IEC 61000-4-30 (Class A measurement
within 10ms), IEC 61000-4-7 (harmonic measurement), and related grid-interoperability standards such as IEEE 1547
and IEC 61851. Beyond power systems, the same principles are equally relevant in IoT applications such as predictive
maintenance, RF and telecoms for envelope tracking, and other sensor-based measurement tasks, such as gas
concentration sensing. These examples highlight the versatility of the CMA as a general-purpose building block for real-
time amplitude, phase, and frequency tracking across many domains.



Author Bio

                                    Dr. Sanjeev Sarpal is a RTEI (Real-Time Edge Intelligence) visionary and expert in signals
                                    and systems with a track record of successfully developing over 26 commercial products.
                                    He is a Distinguished Arm Ambassador and advises top international blue chip companies
                                    on their AIoT/RTEI solutions and strategies for I5.0, telemedicine, smart healthcare, smart
                                    grids and smart buildings.